LOADING
Question

If the fault current is 2000 amp, the relay setting at 50% and CT ratio is 400/5, then the plug setting multiplier will be

A.

25        

B.

10        

C.

50

D.

None of the above

Answer ( Option A)

25        

Solution

Given :Fault current = 2000 amp

Current Transformer (CT) ratio = 400/5

Fault current at secondary side of CT 

Pick up current = Rated current of CT  x  Current setting

= 5 x 0. 5= 2.5A

Now, plug setting multiplier is given by,

Note : Plug Setting Multiplier is unit-less quantity.

Hence, the correct option is (A).